Documents & Evidence

Fire Safety Certificates and Documentation

Essential fire safety documents every building must maintain, from fire licence to suppression system test certificates, with guidance on what each document proves and what gaps to address.

Mandatory Building Owner, FM Team Pending

What Fire Safety Documentation Covers

Fire safety documentation is the paper trail that proves a building can protect its occupants. It encompasses the fire licence issued by the authority, design certificates for fire protection systems, test and commissioning records for alarms and suppression, and ongoing inspection and maintenance logs. Without this documentation, there is no verifiable evidence that life safety systems work as intended.

Fire Licence

Fire Service and Civil Defence (FSCD)
Licence No. FSCD/DMP/2024/XXXX
Building Name / Address ABC Commercial Centre, Motijheel, Dhaka
Building Type Commercial (Office + Retail)
No. of Floors 12 (G+11)
Total Floor Area 8,500 sqm (approx.)
Fire Safety Equipment Extinguishers, hose reels, alarm system, emergency lighting
Issue Date 01 July 2024
Expiry Date 30 June 2025
Issuing FSCD Station Dhaka Metropolitan Fire Station

Why It Matters

Fire is the single most immediate life-safety threat in occupied buildings. In Bangladesh, the Rana Plaza collapse in 2013 and numerous garment factory fires have driven regulatory focus on fire compliance. Multinational corporations conducting pre-lease or acquisition due diligence will always request fire documentation as a first-order requirement. Insurance underwriters base premium calculations and coverage decisions on the quality of fire safety evidence. A building without proper fire documentation is, from a professional standpoint, an uninsurable and unleasable asset.

Key Documents

Fire Licence (FSCD): Issued by the Fire Service and Civil Defence of Bangladesh. Required for all commercial, industrial, and assembly occupancies. Must be renewed annually. The licence confirms that FSCD has inspected the premises and found fire safety measures acceptable. The original licence should be displayed at the main entrance.

Fire Protection System Design Certificate: A document from the fire protection engineer or contractor confirming that the fire alarm, sprinkler, hydrant, and suppression systems were designed in accordance with applicable standards (NFPA 13, NFPA 72, or BNBC Part 4). Should include hydraulic calculations for sprinkler systems and battery backup calculations for fire alarm panels.

Commissioning Certificates: Test records from the initial commissioning of fire alarm panels, smoke detectors, sprinkler systems, fire pumps, hydrant systems, and kitchen hood suppression systems. Each certificate should state the standard tested against, pass/fail results, the testing entity, and the date.

Annual Inspection Reports: Fire extinguisher inspection tags (monthly visual, annual maintenance per NFPA 10), sprinkler system inspection reports (quarterly/annual per NFPA 25), fire alarm panel test reports, emergency lighting test records, and fire door inspection logs.

Fire Drill Records: Documentation of fire evacuation drills including date, time, number of participants, evacuation time achieved, assembly point verification, and corrective actions identified. BNBC and most corporate standards require at least two drills per year.

Fire Risk Assessment: A formal assessment identifying fire hazards, people at risk, existing controls, and recommended improvements. Should be reviewed annually or whenever significant changes occur to the building layout or occupancy.

What to Inspect

Check that fire extinguishers have current inspection tags and are not expired. Verify sprinkler heads are not painted, obstructed, or corroded. Confirm fire alarm panel shows normal status with no fault indicators. Inspect fire doors for self-closing function, intact seals, and no wedging. Verify emergency exit signs are illuminated and exit routes are unobstructed. Check fire pump room for test records posted on the wall.

Common Gaps in Bangladesh

Many buildings in Dhaka have a fire licence but lack the underlying system certificates. Fire alarm panels may be installed but never properly commissioned or regularly tested. Sprinkler systems, where they exist, often lack hydraulic calculation documentation. Fire extinguishers are frequently past their expiry dates or have not been serviced. Fire doors are commonly wedged open or have been modified to remove self-closing mechanisms. Emergency lighting batteries are often dead.

Questions to Ask

  • Is the fire licence current and displayed? When was it last renewed?
  • Can you provide commissioning certificates for the fire alarm and sprinkler systems?
  • What standard were the fire protection systems designed to (NFPA 13, BNBC, or other)?
  • When was the last fire drill conducted and what was the evacuation time?
  • Are fire pump test records available for the last 12 months?
  • Has a formal fire risk assessment been conducted? When was it last updated?

Standards and References

The primary standards governing fire safety documentation include NFPA 1 (Fire Code), NFPA 10 (Portable Fire Extinguishers), NFPA 13 (Sprinkler Systems), NFPA 25 (Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems), NFPA 72 (National Fire Alarm and Signaling Code), and BNBC 2020 Part 4 (Fire Protection). ISO 45001 also requires documented evidence of fire safety management as part of occupational health and safety.

Insights & Guidance

Fire licence from FSCD must be current and displayed System design certificates should reference specific standards (NFPA 13, NFPA 72) Commissioning records prove systems were tested at installation Annual inspection reports are required for all fire protection systems Fire drill records must document evacuation times and corrective actions Many Bangladesh buildings have licences but lack underlying system certificates

Fire documentation is the first item requested in any due diligence process. Without verifiable fire safety evidence, a building cannot be insured at standard rates and may not meet corporate minimum requirements for occupancy. Regulatory enforcement is increasing in Bangladesh following high-profile fire incidents.

Operating without a current fire licence risks closure orders and criminal liability if an incident occurs. Expired fire extinguishers provide false confidence. Uncommissioned fire alarm systems may not activate during a real emergency. Missing sprinkler hydraulic calculations mean there is no proof the system can deliver adequate water to control a fire.

Current fire licence (original displayed, copy on file) Fire protection system design certificates with engineer stamp Commissioning certificates for alarm, sprinkler, pump, and suppression systems Monthly fire extinguisher inspection tags Quarterly/annual sprinkler system inspection reports per NFPA 25 Fire drill records (minimum 2 per year) Fire risk assessment report (reviewed annually)

Fire extinguisher inspection tags should show monthly checks Fire alarm panel should display normal status with no fault lights Sprinkler heads should be clean, unobstructed, and not painted over Fire doors should self-close fully and have intact intumescent seals Exit signs should be illuminated and exit routes clear Fire pump room should have test log posted

Is the fire licence current? When does it expire? Who designed the fire protection systems and to what standard? Can you provide the last 12 months of fire pump test records? When was the last fire drill and what evacuation time was achieved? Has a fire risk assessment been conducted in the last 12 months? Are there any outstanding fire safety deficiencies or notices?

Engage a fire protection engineer when fire systems lack design documentation, when commissioning certificates are unavailable, when the building is changing occupancy type, or when a fire risk assessment has not been conducted. Specialist review is essential before any major renovation that affects fire compartmentation or means of egress.
Was this page helpful?
|

Related Articles

Fire and Life Safety in Buildings

Fire and life safety encompasses detection, suppression, compartmentation and egress. Understanding these interconnected elements is essential for protecting building occupants.

Disclaimer: This article provides educational information and preliminary guidance. It does not constitute professional engineering advice, structural certification, fire-safety approval, legal advice or statutory approval. Building conditions vary by jurisdiction, design, construction and operation. Qualified professionals and relevant authorities should be engaged where required.